Mechanical Pipework

Materials


  • Pipework used for the installation of mechanical systems must be approved and can be either copper, stainless steel, mild steel or HDPE.
  • Pipework made from Acrylonitrile Butadiene Styrene (ABS) or Aquatherm (PP-R) must not be used.



Supports


  • Pipework must be neatly set out, level and parallel with walls/other services.
  • Support spacing of pipework must be located at centres in accordance with the following standards (which are summarised in Appendix 3 and 4) or where recommended by the piping materials manufacturer:
  • Steel pipe to AS 4041 Table 3.28.2.
  • Copper pipes to AS 4809 Table 6.2.
  • Other nonferrous pipe to AS 3500.1 Table 5.6.4.



Expansion Devices


  • Expansion devices for pipework must be:
  • Detailed and installed as per approved shop drawings
  • Installed as per manufacturer’s specifications.



Insulation


  • Pipework must be insulated, including:
  • Heat and chilled water piping and associated fittings
  • Refrigerant suction lines
  • Refrigerant liquid lines
  • Condensate lines



UV Protection


  • Pipework, conduits and insulation exposed to sunlight / ultra violet light must be UV stable or protected to prevent degradation.



Testing


  • Pipework must be tested for a period of 2 hours minimum with a pressure of 1.5 times the working pressure of the system or as per specification.