Mechanical Pipework
Materials
Pipework used for the installation of mechanical systems must be approved and can be either copper, stainless steel, mild steel or HDPE.
Pipework made from Acrylonitrile Butadiene Styrene (ABS) or Aquatherm (PP-R) must not be used.
Supports
Pipework must be neatly set out, level and parallel with walls/other services.
Support spacing of pipework must be located at centres in accordance with the following standards (which are summarised in Appendix 3 and 4) or where recommended by the piping materials manufacturer:
Steel pipe to AS 4041 Table 3.28.2.
Copper pipes to AS 4809 Table 6.2.
Other nonferrous pipe to AS 3500.1 Table 5.6.4.
Expansion Devices
Expansion devices for pipework must be:
Detailed and installed as per approved shop drawings
Installed as per manufacturer’s specifications.
Insulation
Pipework must be insulated, including:
Heat and chilled water piping and associated fittings
Refrigerant suction lines
Refrigerant liquid lines
Condensate lines
UV Protection
Pipework, conduits and insulation exposed to sunlight / ultra violet light must be UV stable or protected to prevent degradation.
Testing
Pipework must be tested for a period of 2 hours minimum with a pressure of 1.5 times the working pressure of the system or as per specification.