Expansion

Why is expansion a consideration?


All roof sheeting and accessories expand and contract with changes in temperature, significant changes in length can occur in very long runs of roofing.


On a clear hot summer day, with no wind, the temperature in roof cladding can reach up to 80°C.


As shown in the table below, the expansion and contraction of metal sheeting and flashings can as high as 27 mm in any 30 m length with an increase of 75 degrees, so the inclusion of appropriate expansion joints is a must.

Roof Expansion Joints


Flashing must have expansion joints:

  • At a maximum of every 24 metres (pierce fixing).
  • Minimum overlap of 250 mm
  • As per Figure

Flashing Expansion Joints


Flashing must have expansion joints:

  • At a maximum of every 12 metres,
  • Within 1000 mm of a corner,
  • Minimum lap of 100 mm
  • As per Figure