Exhaust Systems

Commercial Systems


  • Ductwork for commercial kitchens in accordance with Clause 6.2 of AS1668.1 must have:
  • Galvanized steel ductwork of a thickness not less than 1.2 mm or stainless steel not less than 0.9 mm
  • Joints which are grease tight
  • Fall towards the extraction hood
  • Flexible connections which are grease proof and not longer than 300mm
  • Ceiling access panels which provide unhindered access to the kitchen exhaust
  • A grease proof plug for drainage at the bottom of the vertical shaft
  • Clean out access panels large enough to enable cleaning of ducts which are located:
  • At the bottom of a shaft along the side of ductwork.
  • At every change of direction along the side or top of ductwork.
  • Every 3m in straight runs along the side or top of ductwork.


  • Kitchen exhaust systems must be:
  • Protected with sprinklers when located in a building required to have sprinkler protection, and
  • Have sprinklers installed under kitchen hoods and within kitchen exhaust ductwork.