Exhaust Systems
Commercial Systems
- Ductwork for commercial kitchens in accordance with Clause 6.2 of AS1668.1 must have:
- Galvanized steel ductwork of a thickness not less than 1.2 mm or stainless steel not less than 0.9 mm
- Joints which are grease tight
- Fall towards the extraction hood
- Flexible connections which are grease proof and not longer than 300mm
- Ceiling access panels which provide unhindered access to the kitchen exhaust
- A grease proof plug for drainage at the bottom of the vertical shaft
- Clean out access panels large enough to enable cleaning of ducts which are located:
- At the bottom of a shaft along the side of ductwork.
- At every change of direction along the side or top of ductwork.
- Every 3m in straight runs along the side or top of ductwork.
- Kitchen exhaust systems must be:
- Protected with sprinklers when located in a building required to have sprinkler protection, and
- Have sprinklers installed under kitchen hoods and within kitchen exhaust ductwork.