Have spare conduits labelled, equipped with draw wire and be sealed at both ends.
Maintain a separation from LV or HV power cabling in accordance with the Table 4 of AS/CA S009:2013 outlined below (i.e. underground customer cabling separation from power cabling).
Below Ground Cover
Comms pits to be labelled, free of debris and sitting on a gravel bed of no less than 300mm and / or provided within drainage to the stormwater system
Communication services installed below ground must have minimum depths of (refer table):
Above Ground Clearances
Communication systems installed above ground must maintain a separation from other services in accordance with above ground separation distances or manufacturer’s specifications.
Services Crossover
Separation distances outlined in Appendix 1 and 2 or as per manufactures specifications must be maintained where services cross over.
Cable Supports
Communication cabling must:
Be installed in accordance with the cable manufacturer’s instructions.
Be supported on cable trays, catenary supports or baskets.
Be strapped to the soffit which must:
Have no more than 24 cables bunched together or as per manufacturer specifications.
Have spans between soffit clips sufficient such that cabling does not sag in between clips.
Have approved cable fasteners installed:
At intervals that comply with Table 8.1 of AS/NZS 3084 .
In accordance with the manufacturer’s specified spacing.
Using velcro fastening type. Nylon/zip style cable ties are not to be used.
Seismic
Seismic restraints/bracing in accordance with AS1170.4 - 2007 must be:
Detailed and installed as per approved shop drawings.
Installed for communications systems such as cable systems, motor control devices, switchgear, transformers and unit substations.
Separation between restrained and unrestrained services must be in accordance with the table below: